Automatic Venetian Blind Tilt with a 35 mm KNX Tubular Motor

Using an external illuminance sensor to control daylight through adjustable slats

A window can provide useful daylight and an uncomfortable patch of direct sun at the same time. For an office desk, classroom table or hotel seating area, the useful adjustment is often a change in the Venetian blind’s slat angle. The blind can remain lowered while its slats rotate to admit more light or intercept a direct beam.

This article describes a SIXINSMART application concept built around a 35 mm KNX tubular motor, a compatible Venetian blind and an external illuminance sensor. The sensor supplies a light reading. A configured KNX control function decides when adjustment is needed. The motor then drives the blind mechanism through a controlled tilt movement. The aim is responsive daylight control with a clear relationship between the measured input and the physical result.

Why slat tilt matters

A Venetian blind has two different adjustments: the height of the blind and the angle of its slats. Raising the bottom rail exposes more of the window. Tilting the slats changes the openings between them and the directions from which direct light can pass through those openings.

These adjustments serve different purposes. A lowered blind can keep a strong beam away from a seated occupant while admitting daylight between partly open slats. More open slats can preserve a view and increase light admission when conditions allow. Depending on their finish and orientation, slats can also reflect some incident light toward room surfaces.

The useful setting depends on the window orientation, sun direction, slat geometry and the position of the person using the room. PNNL’s guidance on window attachments and solar control describes daylight, glare, views and solar gains as related design considerations. Here, we focus on the slat adjustment that changes the room’s daylight conditions.

The SIXINSMART motor and sensor arrangement

Figure 1. Functional system arrangement. The control logic runs in a suitable KNX device or automation controller; it is a required function, not necessarily a separate enclosure. Motor power and KNX bus power follow their respective specifications.

The drive at the center of this application is a 35 mm KNX tubular motor assembly. SIXINSMART’s 35 mm DC24V KNX tubular motor provides one documented example in the range, describing jog and tilt adjustment for Venetian blinds. The selected motor, drive adapter and headrail mechanism must work together to turn the slats. Motor diameter alone does not establish this mechanical compatibility.

For the externally interfaced tubular motor arrangement described in SIXINSMART’s KNX motor module manual, the KNX module connects the motor to the building bus. This article therefore treats the module as part of the motor assembly. The motor’s operating supply is separate from the KNX communication bus.

An external sensor means a separate sensing device. In this arrangement, a SIXINSMART SS3020.0201 outdoor illuminance sensor measures the light at the relevant facade. Its user manual specifies a 1–64,000 lux measuring range and KNX output of illumination values. It supplies the input for the proposed control strategy.

The integration task is to connect the sensor value to a defined shading rule and then connect that rule to a verified motor action. A sensor and motor sharing the KNX bus do not establish the rule automatically. The project must specify which device executes it, which commands it sends, and how manual operation takes priority.

How changing the slat angle changes light admission

Figure 2. Simplified side views with the incoming light direction held constant. Rays end where a slat intercepts the direct path; reflected and scattered light are omitted. The illustrated angles are geometry examples, not motor commands or accuracy specifications.

Consider the blind at a fixed height. When its slats are relatively open, a range of direct light paths can pass between them. Rotating the slats changes that range. A path that previously reached a desk may then meet a slat instead.

This is the physical basis of the proposed automatic adjustment. The illuminance signal indicates changing light conditions; the control function selects a more open or more shielding tilt setting; the motor produces the movement through the blind’s mechanism.

The sensor reports illuminance in lux. It does not report the sun’s azimuth or elevation. Accordingly, this is illuminance-triggered slat adjustment. A strategy that tracks the sun’s direction requires additional information, such as location, date, time and facade orientation, together with appropriate control logic.

A motor movement also does not change the direction of sunlight arriving at the building. It changes which paths the blind admits, intercepts or redirects. Describing the result this way makes the connection between the sensor, mechanism and daylight easier to test.

Turning a light reading into a tilt action

A practical starting strategy uses a small set of calibrated tilt states. For example, commissioning can establish a daylight state, an intermediate state and a stronger shielding state. These names describe observed blind settings; they do not imply three built-in motor presets.

The control function maps stable sensor conditions to one of those states. The motor action used to reach each state must be established on the actual blind. Where the verified KNX command path supports jog operation, short, bounded movements can provide incremental adjustment. Commissioning must confirm the direction, step behavior, stop response and repeatability through that KNX path.

A travel percentage is not automatically a slat angle. An object reporting 50 percent travel cannot be relabeled as 45 degrees of slat tilt without a validated mechanical relationship. Similarly, recording an issued command does not prove that the slats reached the intended orientation. The published motor technical manual describes travel control and status; independent slat-angle feedback must be established for the selected configuration before it is claimed.

A stable control policy also needs hysteresis and timing. Use different conditions to enter and leave a shielding state, so a reading near one boundary does not repeatedly reverse the motor. Require the new condition to persist, allow the movement to settle, and set an appropriate interval before another automatic adjustment. Determine those settings from the actual blind, sensor reporting rate and acceptable occupant experience.

Figure 3. Proposed control policy with symbolic thresholds. Values, movement sequences and timings are project settings. This diagram does not assert that the sensor or motor contains this complete algorithm.

For an outdoor sensor, continued high illuminance must not cause endless closing steps: tilting an indoor blind will not reduce the outdoor reading. Once the selected tilt state has been reached through the calibrated sequence, the controller holds it until conditions justify a new state. After manual movement or a loss of the assumed starting state, the automatic sequence must re-establish its reference before relying on counted steps.

Selecting the correct sensor output

The SS3020.0201 technical manual identifies a brightness value object using DPT 9.004, and a separate threshold switching object using DPT 1.001. These outputs serve different purposes: one communicates a numerical illuminance reading, while the other communicates a binary condition.

For the multi-state strategy in this article, use the numerical reading as the input to the selected shading logic. Confirm its supported input type in ETS. Do not connect a lux value directly to a motor position object, or assume that a sensor’s on/off telegram is a compatible slat command merely because both devices use KNX.

The published sensor manual lists a 60–1,000 lux setting range for its built-in threshold switch. That is different from the sensor’s measuring range. A strategy using higher facade thresholds therefore needs a suitable logic function that evaluates the measured value. The final threshold values belong to project commissioning and should reflect the installed sensor’s location.

What the sensor location changes

Figure 4. Outdoor reference sensing and indoor feedback answer different questions. The indoor arrangement requires an appropriate indoor sensor; it is not a claim that the outdoor SS3020 should be installed as a workplane sensor.

An outdoor facade sensor provides a reference for the light reaching that side of the building. Its reading can select a shielding state even before an occupant adjusts the blind. The location should represent the controlled windows and follow the sensor’s mounting instructions, avoiding irrelevant light sources or temporary shading that would distort the input.

A separate illuminance sensor installed inside the room would support a different objective. It could measure a representative occupied area and provide feedback after the blind moves. Maintaining an indoor target then requires a controller that accounts for the blind’s effect on the reading, electric lighting and the time needed for conditions to settle.

For this application, the main arrangement uses the external facade sensor to select calibrated tilt states. Indoor readings are useful for checking the outcome. If the project objective later becomes maintaining a chosen indoor illuminance band, that is a separate control requirement to implement and validate.

Commissioning the complete blind

Begin with the assembled blind. Confirm that the selected 35 mm motor and transmission provide the required tilt motion, establish the permitted movement range, and check how tilt and lifting interact. A mechanism may briefly reverse or move before a desired orientation is reached; the control strategy must reflect the mechanism actually installed.

Next, verify the KNX path. Import the matching application, test the relevant movement and stop objects, and observe the physical response. Confirm jog or short-operation behavior over KNX before enabling the automatic rule. A successful remote-control tilt test alone does not verify this communication path. Record the tested firmware, database and motor combination.

Set up the sensor reporting and the control function, then test the calibrated states at a consistent blind height. Record the facade reading, issued command or sequence, observed slat state and indoor light reading. When testing successive settings outdoors, record the changing external conditions as well; a passing cloud can otherwise look like an effect of the blind.

Finally, test manual override, return to automatic mode, loss of the sensor value and restoration of power. Define the response explicitly. An occupant’s manual adjustment should not be immediately reversed by the next routine sensor update. Fault handling and mechanical limits must remain effective in every mode.

A real building automation example for STEM learning

This application makes a useful demonstration because learners can follow the full chain from measurement to a visible mechanical result. The subject remains the real KNX motor and Venetian blind. A prepared demonstration rig lets an instructor show what the sensor reports, how a rule uses that information and how the slats change the light pattern.

An observation exercise can compare the calibrated states while the blind height remains fixed. Learners record the external lux value, measure the slat orientation where practical, and compare indoor illuminance at the same location. They can then explain why two different slat settings may provide similar desk readings while producing different direct-light patterns or views.

A second exercise introduces a brief change in the sensor condition. Learners compare immediate switching with a rule that includes persistence and hysteresis. The question is whether each movement corresponds to a useful change in conditions. Use a prepared installation under an instructor’s supervision, with live power connections and the moving mechanism kept inaccessible.

These activities connect sensing, communication, mechanical movement and experimental reasoning without requiring invented performance results.

Planning a project with SIXINSMART

Start with the Venetian blind mechanism and the desired daylight behavior. Provide SIXINSMART with the blind dimensions, headrail details, required lift and tilt operation, motor supply, sensor location and KNX control environment. That information allows the motor assembly and command path to be checked against the application.

The useful project outcome is a defined and repeatable relationship between light conditions and slat movement. A 35 mm KNX tubular motor provides the drive, the external sensor supplies the input, and the commissioned control function coordinates the response. Review the 35 mm motor range, Venetian blind application guide and KNX technical downloads when selecting the hardware for that relationship.