Description
Engineered for High-Reliability Electrical Control: The 4-Channel 10A KNX Switch Actuator
In the demanding field of commercial building integration, specifying the right switching hardware is critical to the longevity and stability of the entire automation network. The SIXINSMART 4-Channel 10A KNX Switch Actuator (G-NR4.10.1) is a highly integrated, modular relay controller designed exclusively for the KNX/EIB standard. Tailored for system integrators, electrical contractors, and wholesale distributors, this 4-fold DIN rail actuator provides independent, uncompromising control over standard electrical circuits. By combining high-capacity standalone relays with an advanced internal logic engine, it transforms conventional electrical loads into intelligent, manageable nodes within a centralized Building Management System (BMS).
Universal Load Compatibility and High-Endurance Relays
The core strength of the G-NR4.10.1 lies in its robust output stage. Each of the 4 independent channels is equipped with a premium-grade standalone relay rated for 10A at 230VAC, supporting a maximum total actuator current of 40A. Unlike entry-level switches that degrade under complex electrical stress, this actuator is explicitly engineered to handle a diverse range of applications. It is fully certified for switching Resistive loads, Capacitive loads, Inductive loads, and modern LED power supplies. This universal compatibility ensures that whether you are switching heavy-duty office lighting, motor-driven extraction fans, or complex capacitive LED driver arrays, the relay contacts resist welding and degradation, boasting an exceptional mechanical life of 1,000,000 operations.
Streamlined Architecture: Bus-Powered & Space-Optimized
Panel space and wiring complexity are major cost drivers in commercial electrical installations. The SIXINSMART 4-Channel Actuator addresses these pain points through a highly optimized architectural design. Housed in a compact 4SU (72mm) wide enclosure, it snaps directly onto standard 35mm DIN rails (EN 60715), conserving critical space in crowded distribution boxes. Furthermore, the entire module is powered directly through the KNX/EIB bus (consuming <150mW). By eliminating the need for an auxiliary 24V or 230V power supply to drive the internal electronics, integrators can significantly reduce copper wiring, eliminate a potential point of hardware failure, and streamline the overall cabinet layout.
Advanced Decentralized Logic and PWM Heating Integration
To ensure lightning-fast response times and prevent KNX bus saturation, the G-NR4.10.1 decentralizes processing by executing complex automation commands locally. The onboard processor supports vast Scene Group Control (16 groups, 64 scenes each) and intricate Sequence Control (5 sequences, 16 steps each) for dynamic architectural environments. Beyond simple on/off switching, the device features a specialized Heating Function, outputting a precise PWM (1-bit/1-byte) control signal. This allows designated channels to seamlessly drive proportional thermoelectric valves for underfloor heating or radiator manifolds. Combined with built-in Logical Functions (AND, OR, XOR, Logic Gates) and Threshold Functions (High/Low, Hysteresis), this actuator serves as a multi-disciplined control hub for both lighting and HVAC ecosystems.
Proactive Diagnostics and Fail-Safe Operations
Maintaining system uptime in luxury hotels, hospitals, and corporate headquarters requires proactive hardware. This actuator is equipped with comprehensive Control Functions designed to keep the BMS informed. It features autonomous Channel Status Responses, Time-Delayed Transmissions, and continuous Heartbeat Packet Transmissions to verify network integrity. In the event of a power outage, the customizable Power-Up Recovery settings dictate exactly how each relay should behave upon power restoration, preventing electrical surges and ensuring facility safety. Additionally, hardcoded Time Functions (Time-Delay, Flashing, Stairwell Lighting) provide instant, reliable templates for security and transit zone automation.
Verbatim Technical Parameters (G-NR4.10.1 Specification)
The following engineering parameters replicate the manufacturer’s technical datasheet to ensure absolute accuracy for project specification and electrical cabinet design.
| Category | Parameter Name | G-NR4.10.1 |
|---|---|---|
| Basic Parameters |
KNX Bus Voltage | 30VDC |
| KNX Bus Current | <5mA | |
| KNX Bus Power Consumption | <150mW | |
| Output Switching Performance |
Number of Switching Output Channels | 4 |
| Output Tytle | Standalone Relay | |
| voltage | 230VAC@50Hz | |
| load current | 10A | |
| The maximum total current allowed by the entire actuator | 40A | |
| Output Life | Mechanical Life | 1000000ops |
| Electrical Life | 100000ops | |
| Operation and Display |
Programming Button | Set Physical |
| Manual Button/LED Indicator | Manual Control and Indication | |
| Environment | Ta/Operation Tempe | -5~+45°C |
| Ts/Storage Temp | -20~+60°C | |
| Operating Humi | 10~95% RH Condensation-Free | |
| Safety&EMC | Safety Standards | IEC 60669-2-1:2021, IEC 60669-1:2017, IEC 63044-3:2017, EN 50491-2:2010 + A1:2020, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019, EN IEC 60669-2-1:2022 |
| Electromagnetic Compatibility Emission | IEC 63044-3:2017,EN IEC 63044-5-1:2019;EN IEC 63044-5-2:2019, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019 | |
| Electromagnetic Compatibility Immunity | IEC 63044-3:2017, EN IEC 63044-5-1:2019; EN IEC 63044-5-2:2019, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019 | |
| Withstand Voltage | KNX Between Ports and Relay Terminals: 2KVAC | |
| Other | Screw Terminal | Stranded Wire, 0.5-4.0mm² Solid Wire, 0.5-2.5mm² |
| KNX Bus Terminal | 0.8mm , Solid Wire | |
| Dimension | 72*90*64.3mm | |
| Face Width | 4SU | |
| Install | 35mm DIN Rail Mounting |
Remark: Unless otherwise specified, all specifications are measured at 230VAC input, rated load, and an ambient temperature of 25°C. Provide the test report issued by a certification body.
System Integrator FAQ: 4-Channel KNX Switch Actuators
Q1: How does the G-NR4.10.1 handle the high inrush currents typical of modern LED power supplies?
A: Modern capacitive LED drivers generate significant inrush currents during startup, which can weld standard relay contacts. The G-NR4.10.1 utilizes high-quality standalone relays specifically engineered to be suitable for Capacitive, Inductive, and Resistive loads. These robust contacts ensure long-term switching reliability (up to 1,000,000 mechanical operations) even under harsh electrical conditions.
Q2: Does this actuator require an external 24V or 230V auxiliary power supply to operate?
A: No. One of the primary engineering advantages of this module is that the internal electronics are powered entirely and directly through the KNX/EIB bus (drawing <5mA). This eliminates the cost, wiring labor, and cabinet space associated with installing additional auxiliary power supplies, streamlining the distribution board layout.
Q3: Can the actuator be used for HVAC control as well as lighting?
A: Yes. The device features a versatile PWM (1-bit/1-byte) Heating Function. Integrators can assign specific relay channels to output Pulse Width Modulation signals, which accurately control thermoelectric valves in underfloor heating systems or radiator circuits. This dual-purpose capability makes it an exceptionally cost-effective node for complete room automation.
Q4: How do the manual control buttons assist during the project construction phase?
A: The front panel includes dedicated manual override buttons and LED status indicators for each of the 4 channels. During the construction phase, before the ETS programming is downloaded or the KNX bus is fully commissioned, electrical contractors can manually actuate the relays to test load wiring and verify circuit integrity directly at the distribution board.
Q5: Is the logic processing handled centrally or locally on the actuator?
A: The G-NR4.10.1 features decentralized processing. It executes Logical Functions (AND, OR, XOR), Threshold Functions (High/Low, Hysteresis), and Time Functions (Stairwell lighting, Flashing) locally on the device hardware. This significantly reduces telegram traffic on the KNX bus and ensures immediate execution of automation routines without relying on a central logic server.