8-Channel 16A KNX Switch Actuator G-NR8.16.1 | DIN Rail High-Load Relay for Professional Building Automation & ETS6 Programming

01
Industrial-Grade Switching

Features 8 independent 16A relay channels engineered for heavy resistive, capacitive, and inductive loads. Fully optimized for high-inrush LED power supplies and industrial switching requirements.

02
Embedded Logic Engine

Built-in logical functions (AND, OR, XOR) and Logic Gate processing. Empower your smart building with decentralized automation logic directly within the actuator, reducing system complexity.

03
HVAC & Climate Control

Professional PWM (1-bit/1-byte) control output and hysteresis threshold functions. Ideal for underfloor heating, valve control, and climate management in high-end commercial projects.

04
Complex Scene Management

Supports 16 scene groups (64 scenes each) and 5 sequence functions with 16 steps each. Precision lighting control and power sequencing for complex architectural environments.

05
Global Project Reliability

Compact 8SU DIN rail design (35mm) with manual override and status LEDs. ETS5/ETS6 ready with a 3-year warranty, adhering to strict IEC and EN safety standards.

06
Bus-Powered Efficiency

Ultra-low power consumption (<150mW) powered directly via the KNX/EIB bus. Simplifies wiring in distribution boards by eliminating the need for auxiliary power supplies.

 

Download SIXINSMART G-NR8.16.1 8-channel 16A KNX switch actuator datasheet

Description

Professional 8-Channel 16A KNX Switch Actuator for Integrated Smart Building Systems

The G-NR8.16.1 8-Channel 16A KNX Switch Actuator represents a critical component for modern electrical engineering and building automation. Designed for wholesalers, system integrators, and electrical contractors, this actuator provides high-density switching capabilities within a compact DIN-rail footprint. Every channel is isolated and equipped with premium individual relays capable of managing 16A loads, ensuring long-term reliability in demanding environments such as luxury hotels, commercial offices, and industrial facilities.

Comprehensive Technical Specifications (Model: G-NR8.16.1)

As a core element of the KNX/EIB ecosystem, the G-NR8.16.1 is engineered for seamless integration and robust performance. Below are the complete and detailed technical parameters strictly verified for this specific 8-channel, 16A actuator model.

Parameter Category Parameter Name G-NR8.16.1 Specifications
Basic Parameters KNX Bus Voltage 30VDC
KNX Bus Current <5mA
KNX Bus Power Consumption <150mW
Number of Switching Output Channels 8
Output Type Standalone Relay
Output Switching Performance Voltage 230VAC@50Hz
Load Current 16A
Maximum Total Current Allowed by Entire Actuator 128A
Output Life Mechanical Life 1,000,000 ops
Electrical Life 50,000 ops
Operation and Display Programming Button Set Physical
Manual Button / LED Indicator Manual Control and Indication
Environment Ta/Operation Temp -5 ~ +45℃
Ts/Storage Temp -20 ~ +60℃
Operating Humi 10 ~ 95% RH Condensation-Free
Safety & EMC Safety Standards IEC60669-2-1:2021, IEC 60669-1:2017, IEC63044-3:2017, EN 50491-2:2010 + A1:2020, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019, EN IEC 60669-2-1:2022
Electromagnetic Compatibility Emission IEC63044-3:2017, EN IEC 63044-5-1:2019; EN IEC 63044-5-2:2019, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019
Electromagnetic Compatibility Immunity IEC63044-3:2017, EN IEC 63044-5-1:2019; EN IEC 63044-5-2:2019, EN IEC 63044-3:2018, EN IEC 63044-5-1:2019, EN IEC 63044-5-2:2019
Withstand Voltage KNX Between Ports and Relay Terminals 2KVAC
Other Specifications Screw Terminal 0.5 – 4.0mm² Solid Wire, 0.5 – 2.5mm² Stranded Wire
KNX Bus Terminal 0.8mmφ, Solid Wire
Dimension 144*90*64mm
Face Width 8SU
Install 35mm DIN Rail Mounting

* Remark: Unless otherwise specified, all specifications are measured at 230VAC input, rated load, and an ambient condition as specified.

Advanced Functional Description

The G-NR8.16.1 is more than a simple relay module; it is a programmable logic controller for electrical circuits. B2B integrators can leverage a suite of built-in firmware features to optimize energy efficiency and user experience:

  • Scene Group Control: Manage complex lighting moods across 16 scene groups, with each group supporting up to 64 individual scenes. This is vital for hotel ballroom or theater lighting scenarios.
  • Sequence Control: Execute 5 different sequence functions. Each sequence can handle 16 specific steps, allowing for staggered power-ups of heavy industrial equipment to prevent voltage sags.
  • Intelligent Time Functions: Features include Time-Delay Control, Flashing Control for signaling, and a dedicated Stairwell Lighting Function with programmable warning periods.
  • Embedded Logical Operations: The unit includes AND, OR, XOR, and Logic Gate functions. This allows the installer to create complex local automation logic directly within the actuator.
  • HVAC Heating Control: Supports PWM (Pulse Width Modulation in 1-bit or 1-byte formats) and Threshold Functions (High/Low, Hysteresis control). Excellent for managing thermal actuators in floor heating systems.
  • Advanced Control Capabilities: Features Channel Status Response, Time-Delayed Transmission, Heartbeat Packet Transmission, and configurable Power-Up Recovery states.

B2B Project Applications

For engineering firms and procurement professionals, the 16A rating of the G-NR8.16.1 is a significant differentiator. Modern LED drivers often generate high inrush currents that can weld contacts on standard 10A relays. Our 16A high-performance relays are specifically tested for:

  • Commercial LED Lighting: Safe switching of large banks of LED panels and high-output drivers.
  • Inductive Motor Loads: Reliable control of small ventilation fans, motorized curtains, and blinds.
  • Capacitive Power Supplies: Robust performance when interfacing with switched-mode power supplies (SMPS) commonly found in server rooms.

Installation & Maintenance

Designed with the installer in mind, the 35mm DIN rail mounting and 8SU face width ensure a secure fit into any standard electrical distribution board. The physical programming button and manual override LED indicators allow for testing and commissioning even before the KNX system is fully programmed via ETS.

B2B Technical Support: We offer a 3-year comprehensive warranty. Programmable via ETS5/ETS6 software, bulk procurement options and tailored technical database support for large-scale integration projects are available globally.

Frequently Asked Questions for KNX System Integrators & Wholesalers

1. Is the G-NR8.16.1 compatible with the latest ETS6 software?

Yes, our 8-channel KNX switch actuator is fully compatible with both ETS5 and ETS6. We provide the necessary .knxprod database files for easy integration and parameter configuration.

2. Can this actuator handle high-inrush current from LED drivers?

Absolutely. The 16A rated relays in the G-NR8.16.1 are engineered to handle the capacitive inrush current typical of modern LED power supplies, preventing relay contact welding and ensuring long-term durability in commercial projects.

3. Does the module require an external power supply?

No. The module is powered entirely through the KNX/EIB bus. This simplifies the wiring in the distribution box as you only need to connect the KNX bus cable and the load circuits.

4. How do the logical functions help in building automation?

The integrated AND, OR, and XOR gates allow for decentralized logic. For example, you can program the actuator to only turn on outdoor lighting if both a “Night” signal and a “Motion” signal are received, without needing a separate logic module.

5. What is the warranty period for bulk B2B orders?

We provide a standard 3-year warranty. For large-scale engineering projects and wholesalers, we also offer extended technical support and priority replacement services to ensure project continuity.

6. Can I manually control the channels during site commissioning?

Yes. The G-NR8.16.1 features manual push buttons on the front panel for each channel. This allows electricians to test the load circuits before the KNX bus is fully commissioned.